Aligned PHX Union Hills
Aligned Data Centers · PHX-01/02/03
- IT live
- 120 MW
- Free to lease
- 14.4 MW
- $ / kW·mo
- —
- White space
- 703k ft²
Inventory
88% occupiedPower
120 MWlive
14.4 MW to lease · 106 MW in use
White space
703k ft²total
45k ft² free · 658k ft² occupied
65k m² · 4,181 m² free
Free power is unsold critical IT at this building, not utility headroom. Space is computer-room white space.
Power
About 105 MW of the utility feed is cooling, conversion, and house load.
Power cost
—/kW·mo
— industrial
- Per MW·year
- —
- This site · 120 MW
- —
Market industrial · utility tariff × PUE, not colo list price.
- Redundancy
- 2N
- Opened
- 2017
- Renewable match
- 40%
- Rack density
- 30 kW
- PUE
- 1.151.00 ideal · 1.60 typical
- Power source
- APS / SRP. Dual 69 kV inlets. Desert dry-cooler campus.
Cooling
Plant
Evaporative
Liquid
Deployed
Rack density
30 kW
H100-eq
—
WUE
—
Operator has not published WUE. Blank, not zero — air-cooled sites still use some water.
Aligned DeltaFlow near-zero-water cooling plus liquid-ready manifolds for AI cabinets.
Network carriers
4On-net and metro carriers typically present at this location, including internet exchanges. Not a full circuit inventory.
Clouds
4Native regions and typical Direct Connect / ExpressRoute / Interconnect on-ramps at this campus. Availability varies by hall.
Location
Phoenix, Arizona, United States
2500 W Union Hills Drive, Phoenix, AZ
33.655°, -112.111° · North America
Tenants / users
Hyperscale, cloud, AI
Notes
55-acre Union Hills campus. Advanced Cooling Lab on site. Complements DAL-01 already in the index. Macquarie-backed.
Compiled from public filings, operator pages, and reporting. Not an official operator specification.