Operational
Colocation
Liquid cooling
Tier III

Aligned DAL-01

Aligned Data Centers · Dallas

IT live
50 MW
Free to lease
6 MW
$ / kW·mo
$55
White space
156k ft²

Inventory

88% occupied

Power

50 MWlive

6 MW to lease · 44 MW in use

White space

156k ft²total

19k ft² free · 138k ft² occupied

15k m² · 1,742 m² free

Free power is unsold critical IT at this building, not utility headroom. Space is computer-room white space.

Power

IT live50 MW
Free to lease6 MW
Utility feed100 MW
Campus / planned100 MW

About 50 MW of the utility feed is cooling, conversion, and house load.

Power cost

$55/kW·mo

6.6¢ industrial · 7.6¢ after PUE 1.15

Per MW·year
$665k
This site · 50 MW
$33M/yr
30 kW rack
$1,662/mo
3.2¢ cheapdear 22.4¢

2.1× the cheapest market (Iceland Landsvirkjun). Same IT load there is $17M/yr less.

ERCOT North · utility tariff × PUE, not colo list price.

Redundancy
2N
Opened
2019
Renewable match
30%
Rack density
30 kW
PUE
1.151.00 ideal · 1.60 typical
Power source
Oncor.

Cooling

Plant

Evaporative

Liquid

Deployed

Rack density

30 kW

H100-eq

WUE

Operator has not published WUE. Blank, not zero — air-cooled sites still use some water.

Delta Flow cooling (near-zero water) plus liquid-ready manifolds for AI cabinets.

Network carriers

5

On-net and metro carriers typically present at this location, including internet exchanges. Not a full circuit inventory.

Clouds

3

Native regions and typical Direct Connect / ExpressRoute / Interconnect on-ramps at this campus. Availability varies by hall.

Location

Plano, Texas, United States

Plano, TX

33.008°, -96.757° · North America

Tenants / users

Cloud, enterprise

Notes

Aligned's Delta Flow system is designed to cut water use versus traditional cooling towers.

Operator site

Compiled from public filings, operator pages, and reporting. Not an official operator specification.